The Water Treatment Plant is the main source of water used in the Grhasia
Psychiatric Hospital of DIY, so that water quality must meet the conditions that
have been determined. On examination of Fe levels carried out on January 23,
2019, the results showed that Fe content was 3 mg / l, while the standard Fe
content according to Minister of Health Regulation No. 32 of 2017 concerning
Environmental Health Quality Standards and Water Health Requirements for
Sanitary Hygiene Needs, Swimming Pool, Solus per Aqua, and Public Baths are 1
mg/l.
This study was conducted to determine the ability of the Water Treatment
Plant in the Grhasia Psychiatric Hospital DIY to reduce iron (Fe) levels. This type
of research is a survey with descriptive analysis.
The results of this study include iron content in bore wells on the condition
of 2 rainy days reaching 3.6 mg/l and in the conditions of 2 days no rain reaches
2.3 mg/l. Towards the first groundtank reservoir, in conditions of 2 rainy days iron
content has decreased from 3,6 milligrams per liter to 1.4 milligrams per liter
(61.11%) and in conditions of 2 days no rain has decreased from 2,3 milligrams
per liter to 2.16 milligrams per liter l (6.08%). Go to the aeration tray, during the 2
rainy days conditions the iron content drops from 1.4 milligrams per liter to 1.2
milligrams per liter (14.28%) and at the condition of not 2 rainy days the iron
level drops from 2.16 mg/l to 2 mg/l (7.41%). Towards the coagulationflocculation
bath, in the conditions of 2 rainy days the iron content drops from 1.2
mg/l to 1.06 mg/l (11.67%) and in the conditions of 2 days it does not rain, the
iron content drops from 2 mg/l to 1.86 mg/l (7%). Towards the sedimentation unit,
on the condition of 2 rainy days, the iron content drops from 1.06 mg/l to 0.2 mg/l
(81.13%) and in the conditions of 2 days it does not rain, the iron content drops
from 1.86 mg/l became 0.36 mg/l (80.64%). Towards the filtration unit, the iron
content in the conditions of 2 rainy days has decreased from 0.2 mg/l to 0.1 mg/l
(50%) and in the conditions of 2 days it does not rain, iron content drops from
0.36 mg/l to 0.1 mg/l (72.22%). Towards the second groundtank reservoir, iron
content in conditions of 2 rainy days and 2 days of rain, drops from 0.1 mg/l to 0
mg/l (100%). Towards a water tower, iron content in conditions of 2 rainy days
and 2 days of rain, still 0 mg/l.